Perle UNO-PS /350-900DC/24DC/60W DIN Rail Power ...

SPHINX in Europe
BE
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Product groups > Power Supplies > Perle UNO-PS /350-900DC/24DC/60W DIN Rail Power ...

Perle UNO-PS /350-900DC/24DC/60W DIN Rail Power Supply

Regulated DC to DC Converter

Perle UNO-PS /350-900DC/24DC/60W DIN Rail Power Supply
6603_21675.png
6603_21676.jpg
  • PropertiesProperties
  • DescriptionDescription
  • Further InformationFurther Information
  • PDFPDF
  • 24V DC Output Voltage
  • 2.5 Amps
  • 60 Watts
  • Input Voltage Range: 300 V DC ... 1000 V DC

If you need to efficiently produce a regulated 24 V DC output voltage from a source that may or may not be well controlled to a load that may or may not be constant, the UNO-PS/350-900DC/24DC/60W Power Supply is for you. This DC to DC converter enables direct connection to string voltages of up to 1000 V DC. This means the Combiner Box is supplied directly from the photovoltaic panel and additional installation costs are not incurred. In another expansion stage, the signal line can be replaced by a wireless connection. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, the UNO Industrial DC to DC Converter is designed to meet the needs of your industrial application.


Industrial operating temperature of -25°C to +70°C



Equipment found in traffic management, oil and gas pipelines, weather tracking, industrial and outdoor applications must function in temperatures that cannot be supported by a commercial power supplies. With an operating temperature of -25°C to +70°C, and reliable device start-up at -40°C, the UNO Industrial Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures.


High efficiency over 90% and low no load power consumption



Compared with other products on the market, the UNO Industrial Power Supply provides excellent energy savings. With a very low no load power consumption and over 90% efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making this a very ECO friendly power supply.


Ideal application environments for an UNO DC to DC converter



  • Supply your control cabinet directly from the photovoltaic system to save on installation costs and increase system efficiency.
  • Where an AC connection is not available and direct field installation needed.



Other reasons to choose the UNO DC to DC Converter



  • UL 1741 certification simplifies approval of the overall system
  • LED function monitoring simplifies start-up
  • Minimal space required in the control box
  • High Voltage Isolation input/output value of 8 kV
  • Protections: Short-circuit, Overload, Over voltage, Over-temperature
  • High MTBF (Mean Time Between Failure) values ensue maximum system availability
ProdGrafik

Environmental Product Compliance
REACH SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
General
Net weight 0.3 kg
Efficiency > 90 %
Insulation voltage input/output 8 kV DC (type test)
3 kV DC (routine test)
Protection class II
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1160000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: 0 mm horizontally, 30 mm vertically
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise immunity EN 61000-6-2:2005
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 3)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1.4 GHz ... 2 GHz
Test field strength 3 V/m
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-6-3
EN 61000-4-6
Frequency range 10 kHz ... 80 MHz
Voltage 10 V (Test Level 3)
Standards/regulations EN 61000-4-11
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard - IEC 62109-1
Standard - Electrical safety IEC 62109-1
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL 1741
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to mains voltage dips EN 61000-4-11
Information technology equipment - safety (CB scheme) CB Scheme
Overvoltage category (IEC 62109-1) II
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3
Output data
Nominal output voltage 24 V DC ±1 %
Nominal output current (IN) 2.5 A (-25 °C ... 55 °C)
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series No
Feedback resistance < 35 V DC
Protection against surge voltage on the output ≤ 35 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP (with nominal values)
Output power 60 W
Typical response time < 1 s
Maximum power dissipation in no-load condition < 0.5 W
Power loss nominal load max. < 6.5 W
Dimensions
Width 55 mm
Height 90 mm
Depth 84 mm
Weight per piece 316.9 GRM
Input data
Nominal input voltage range 350 V DC ... 900 V DC
Input voltage range 300 V DC ... 1000 V DC
Dielectric strength maximum ≤ 1050 V DC
Current consumption 0.19 A (350 V DC)
0.07 A (1000 V DC)
Inrush surge current < 1 A (typical)
Choice of suitable circuit breakers 1 A (Characteristic gPV or comparable)
Connection data, onput
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Approvals
  • cULus Recognized
  • EAC
  • UL Recognized
  • cUL Recognized
  • IECEE CB Scheme




Ordering Information

    UNO-PS/350-900DC/24DC/60W Power Supply


        - UNO DC/DC converter with wide range input, for DIN rail mounting, input: 350 ... 900 V DC, output: 24 V DC/60 W


Customers who viewed this item also viewed
Accept all Reject Configure

This website uses cookies to provide the best possible experience. More information.